Differential Feedback
The second PID feedback signal for differential feedback can come from the sources listed in
feedback function is automatically enabled when a differential feedback input is assigned.
Table 5.11 PID Differential Feedback Sources
PID Differential Feedback Source
Settings
Analog Input A1
Set H3-02 = 16 (Differential PID Feedback)
Analog Input A2
Set H3-10 = 16 (Differential PID Feedback)
Analog Input A3
Set H3-06 = 16 (Differential PID Feedback)
Note:
A duplicate allocation of the PID differential feedback input will cause an oPE07 (Multi-Function Analog Input Selection Error) alarm.
5.2 b: Application
208