No.
Parameter Name
Setting Range
Default
E5-02
Motor Rated Power (for PM Motors)
0.10 to 650.00 kW
Determined by
E5-01
n
E5-03: Motor Rated Current (for PM Motors)
Sets the motor rated current in amps. Automatically set when the value is entered to T2-06 during Auto-Tuning.
No.
Parameter Name
Setting Range
Default
E5-03
Motor Rated Current (for PM Motors)
10 to 150% of drive rated
Determined by
E5-01
<1> Display is in the following units:
n
E5-04: Number of Motor Poles (for PM Motors)
Sets the number of motor poles. Automatically set when the value is entered to T2-08 during Auto-Tuning.
No.
Parameter Name
Setting Range
Default
E5-04
Number of Motor Poles (for PM Motors)
2 to 48
Determined by
E5-01
n
E5-05: Motor Stator Resistance (r1) (for PM Motors)
Set the resistance for one motor phase. Do not enter the line-to-line resistance into E5-05 when measuring the resistance
manually.
No.
Parameter Name
Setting Range
Default
E5-05
Motor Stator Resistance (for PM Motors)
0.000 to 65.000 Ω
Determined by
E5-01
n
E5-06: Motor d-Axis Inductance (Ld) (for PM Motors)
Sets the d-Axis inductance in 0.01 mH units. This parameter is set during the Auto-Tuning process.
No.
Parameter Name
Setting Range
Default
E5-06
Motor d-Axis Inductance (for PM Motors)
0.00 to 300.00 mH
Determined by
E5-01
n
E5-07: Motor q-Axis Inductance (Lq) (for PM Motors)
Sets the q-Axis inductance in 0.01 mH units. This parameter is set during the Auto-Tuning process.
No.
Parameter Name
Setting Range
Default
E5-07
Motor q-Axis Inductance (for PM Motors)
0.00 to 600.00 mH
Determined by
E5-01
n
E5-09: Motor Induction Voltage Constant 1 (Ke) (for PM Motors)
Sets the induced peak voltage per phase in units of 0.1 mV/(rad/s) [electrical angle]. Set this parameter when using an IPM
motor with derated torque (SSR1 series or equivalent) or an IPM motor with constant torque (SST4 series or equivalent).
Set the voltage constant with E5-09 or E5-24 when E5-01 is set to FFFF. This parameter is set during Auto-Tuning for PM
motors.
No.
Parameter Name
Setting Range
Default
E5-09
Motor Induction Voltage Constant 1 (for PM Motors)
0.0 to 2000.0 mV/(rad/s)
Determined by
E5-01
Note:
Set E5-24 to 0 when setting E5-09. However, setting both E5-09 and E5-24 to 0 will trigger an alarm. An alarm will also be triggered if
neither E5-09 nor E5-24 are set to 0. When E5-01 is set to FFFF, then E5-09 = 0.0.
n
E5-11: Encoder Z Pulse Offset (ΔΘ) (for PM Motors)
Sets the offset between the rotor magnetic axis and the Z Pulse of the connected encoder. This parameter is set during Auto-
Tuning for PM motors and during Z Pulse Tuning.
5.5 E: Motor Parameters
262
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual