u
F6: Communication Option Card Settings (SI-C3, SI-ET3, SI-N3, SI-P3, SI-S3, SI-T3, SI-
W3)
Parameters F6-01 through F6-03 and F6-06 through F6-08 are used for CC-Link, CANopen, DeviceNet, PROFINET,
LonWorks, PROFIBUS-DP, MECHATROLINK-II, and MECHATROLINK-III options. Other parameters in the F6 group
are used for communication-protocol-specific settings. For more details on a specific option card, refer to the instruction
manual for the option.
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
F6-01
(03A2)
Communications Error
Operation Selection
Comm Bus Flt Sel
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
All Modes
0: Ramp to stop. Decelerate to stop using the deceleration time
in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in
C1-09.
3: Alarm only.
Default: 1
Range: 0 to 3
F6-02
(03A3)
External Fault from
Comm. Option
Detection Selection
EF0 Detection
0: Always Detected
1: Only During Run
All Modes
0: Always detected.
1: Detection during run only.
Default: 0
Range: 0, 1
F6-03
(03A4)
External Fault from
Comm. Option
Operation Selection
EF0 Fault Action
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
All Modes
0: Ramp to stop. Decelerate to stop using the deceleration time
in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in
C1-09.
3: Alarm only.
Default: 1
Range: 0 to 3
F6-04
(03A5)
bUS Error Detection
Time
BUS Err Det Time
All Modes
Sets the delay time for error detection if a bus error occurs.
Default: 2.0 s
Min.: 0.0
Max.: 5.0
F6-06
(03A7)
Torque Reference/
Torque Limit Selection
from Comm. Option
Torq Ref/Lmt Sel
0: Disabled
1: Enabled
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM
CLV/PM
CLV
0: Disabled. Torque reference/limit from option board
disabled.
1: Enabled. Torque reference/limit from option board enabled.
Default: 0
Range: 0, 1
F6-07
(03A8)
Multi-Step Speed
Enable/Disable
Selection when NefRef/
ComRef is Selected
Fref PrioritySel
0: Net/Com REF
1: MultiStep Speed
All Modes
0: Multi-step reference disabled (same as F7)
1: Multi-step reference enabled (same as V7)
Default: 0
Range: 0, 1
F6-08
(036A)
Reset Communication
Parameters
Com Prm Init Sel
0: Init Com Prms
1: No Init Com Prms
All Modes
0: Communication-related parameters (F6-
oo
/F7-
oo
) are
not reset when the drive is initialized using A1-03.
1: Reset all communication-related parameters
(F6-
oo
/F7-
oo
) when the drive is initialized using A1-03.
Default: 0
Range: 0, 1
F6-10
(03B6) CC-Link Node Address CC-Link Node Add
All Modes
Sets the node address if a CC-Link option is installed.
Default: 0
Min.: 0
Max.: 64
F6-11
(03B7)
CC-Link
Communication Speed
CC-Link Baud
0: 156 kbps
1: 625 kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
All Modes
0: 156 Kbps
1: 625 Kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
Default: 0
Range: 0 to 4
F6-14
(03BB)
CC-Link bUS Error
Auto Reset
Bus Err Auto Rst
0: Disabled
1: Enabled
All Modes
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
F6-20
(036B)
MECHATROLINK
Station Address
Station Address
All Modes
Sets the station address when the MECHATROLINK option
has been installed.
Default: 21
Min.: 20
F6-21
(036C)
MECHATROLINK
Frame Size
Frame length
All Modes
Default: 0
Range: 0, 1
B.8 F: Option Settings
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
527