No.
Parameter Name
Setting Range
Default
d6-06
Field Forcing Limit
100 to 400%
400%
u
d7: Offset Frequency
n
d7-01 to d7-03: Offset Frequency 1 to 3
Three different offset values can be added to the frequency reference. They can be selected using digital inputs programmed
for Offset frequency 1, 2, and 3 (H1-
oo
= 44, 45, 46). The selected offset values are added together if multiple inputs are
closed simultaneously. The value is set as a percentage of the Maximum Output Frequency.
Note:
This function can replace the “Trim Control” function (H1-
oo
= 1C, 1D) of older Yaskawa drives.
No.
Parameter Name
Setting Range
Default
d7-01
Offset Frequency 1
-100.0 to 100.0%
0%
d7-02
Offset Frequency 2
-100.0 to 100.0%
0%
d7-03
Offset Frequency 3
-100.0 to 100.0%
0%
illustrates the Offset frequency function.
Frequency
reference
Offset Frequency 1 [d7-01]
(Signed)
Offset Frequency 2 [d7-02]
(Signed)
Offset Frequency 3 [d7-03]
(Signed)
Multi-function
input (44) = on
Multi-function
input (45) = on
Multi-function
input (46) = on
SFS
Frequency
reference after
soft starter
Figure 5.52 Offset Frequency Operation
5.4 d: Reference Settings
250
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual