3.8 Main Circuit Wiring
This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit in
the drive.
NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices
could result in drive malfunction due to loose terminal connections.
NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC bus
charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from switching the
drive on and off more than once every 30 minutes.
u
Main Circuit Terminal Functions
n
Drive Models 2
o
0028 to 2
o
0248 and 4
o
0011 to 4
o
0590
Table 3.2 Main Circuit Terminal Functions
Voltage Class
Three-Phase 200 V
Class
Three-Phase 400 V
Class
Function
Page
Drive Model
2
o
0028 to 2
o
0248
4
o
0011 to 4
o
0590
Terminal
Type
R/L1, S/L2, T/L3
Main circuit power supply input
Connects line power to the drive
U/T1, V/T2, W/T3
Drive output
Connects to the motor
p1, n1
Momentary power loss recovery unit input
DC voltage terminals that connect to a
momentary power loss recovery unit
100 Ω or less
10 Ω or less
Grounding terminal
n
Drive Models 4
o
0720 to 4
o
0930
Table 3.3 Main Circuit Terminal Functions
Voltage Class
Three-Phase 400 V
Class
Function
Page
Drive Model
4
o
0720 to 4
o
0930
Terminal
Type
X, Y, Z
Main circuit power supply
input 1
Power supply input terminals that connect to the harmonic filter
module.
X1, Y1, Z1
Main circuit power supply
input 2
r1/ℓ11, 1/ℓ21, t1/ℓ31
Power supply voltage
detection input
Connects to the harmonic filter module to detects the power supply
voltage order and voltage levels.
U/T1, V/T2, W/T3
Drive output
Connects to the motor
p1, n1
Momentary power loss
recovery unit input
DC voltage terminals that connect to a momentary power loss
recovery unit
p2, n2
DC voltage output
DC voltage terminals that connect to the harmonic filter module
100 Ω or less
Grounding terminal
n
Harmonic Filter Module
Table 3.4 Harmonic Filter Module Main Circuit Terminal Functions
Terminal
Type
Function
Page
R/L1, S/L2, T/L3
Main circuit power supply
input
Connects line power to the harmonic filter module
r1/ℓ11, 1/ℓ21, t1/ℓ31
Power supply voltage
detection input
Connects to drive models 4
o
0720 to 4
o
0930 to detect the power
supply voltage order and voltage levels
X, Y, Z
Filter module output 1
Harmonic filter module output terminals that connect to drive models
4
o
0720 to 4
o
0930.
X1, Y1, Z1
Filter module output 2
p2, n2
DC voltage output
DC voltage terminals that connect to the drive models 4
o
0720 to
4
o
0930
100 Ω or less
Grounding terminal
3.8 Main Circuit Wiring
96
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual