H1 Multi-Function Digital Input Selections
H1-
oo
Setting
Function
LCD Display
Description
Page
20 to 2F External fault
20: NO/Always Det,
Ramp to Stop
21: NC/Always Det,
Ramp to Stop
22: NO/During RUN,
Ramp to Stop
23: NC/During RUN,
ramp to stop
24: NO/ Always Det,
Coast to Stop
25: NC/Always Det,
Coast to Stop
26: NO/During RUN,
Coast to Stop
27: NC/During RUN,
Coast to Stop
28: NO/Always Det,
Fast-Stop
29: NC/Always Det,
Fast-Stop
2A: NO/During RUN,
Fast-Stop
2B: NC/During RUN,
Fast- Stop
2C: NO/Always Det,
Alarm Only
2D: NC/Always Det,
Alarm Only
2E: NO/ During RUN,
Alarm Only
2F: NC/During RUN,
Alarm Only
All Modes
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
30
PID integral reset
PID Intgrl Reset
All Modes
Closed: Resets the PID control integral value.
31
PID integral hold
PID Intgrl Hold
All Modes
Open: Performs integral operation.
Closed: Maintains the current PID control integral value.
32
Multi-Step Speed
Reference 4
Multi-Step Ref 4
All Modes
Used in combination with input terminals set to Multi-Step Speed Reference 1, 2,
and 3. Use parameters d1-09 to d1-16 to set reference values.
34
PID soft starter cancel
PID SFS Cancel
All Modes
Open: PID soft starter is enabled.
Closed: Disables the PID soft starter b5-17.
35
PID input level selection PID Input Invert
All Modes
Closed: Inverts the PID input signal.
40
Forward run command
(2-Wire sequence)
FwdRun 2Wire Seq
All Modes
Open: Stop
Closed: Forward run
Note:
Cannot be set together with settings 42 or 43.
41
Reverse run command
(2-Wire sequence)
RevRun 2WireSeq
All Modes
Open: Stop
Closed: Reverse run
Note:
Cannot be set together with settings 42 or 43.
42
Run command
(2-Wire sequence 2)
Run/Stp 2WireSeq
All Modes
Open: Stop
Closed: Run
Note:
Cannot be set together with settings 40 or 41.
B.9 H Parameters: Multi-Function Terminals