3.
Release the cables from the hooks in 5 locations.
A
A –Hook locations
Figure 7.12 Release the Cables
4.
Loosen the 4 screws affixing the cooling fan unit.
A
A –Screw locations
Figure 7.13 Remove the Cooling Fan Unit
5.
Disconnect the 3 pluggable connectors and remove the fan unit from the drive.
Figure 7.14 Unplug the Relay Connectors
n
Installing the Cooling Fan Unit
1.
Connect the relay connectors for the fans in the replacement fan unit.
Note:
Replace the whole unit when performing maintenance on the cooling fans.
7.4 Drive Cooling Fans