1.2 General Description
u
U1000 Model Selection
for drive selection depending on Normal Duty (ND) or Heavy Duty (HD) rating.
Note:
The models and capacities in shown here are based on standard settings and operation conditions. Higher carrier frequencies and higher
ambient temperatures require derating.
Table 1.1 U1000 Models
Three-Phase 200 V Class
Three-Phase 400 V Class
Drive Model
Heavy Duty Rating Normal Duty Rating
Drive Model
Heavy Duty Rating Normal Duty Rating
Rated Output
Current (A)
Rated Output
Current (A)
Rated Output
Current (A)
Rated Output
Current (A)
2
o
0028
22
28
4
o
0011
9.6
11
2
o
0042
28
42
4
o
0014
11
14
2
o
0054
42
54
4
o
0021
14
21
2
o
0068
54
68
4
o
0027
21
27
2
o
0081
68
81
4
o
0034
27
34
2
o
0104
81
104
4
o
0040
34
40
2
o
0130
104
130
4
o
0052
40
52
2
o
0154
130
154
4
o
0065
52
65
2
o
0192
154
192
4
o
0077
65
77
2
o
0248
192
248
4
o
0096
77
96
–
–
–
4
o
0124
96
124
–
–
–
4
o
0156
124
156
–
–
–
4
o
0180
156
180
–
–
–
4
o
0216
180
216
–
–
–
4
o
0240
216
240
–
–
–
4
o
0302
240
302
–
–
–
4
o
0361
302
361
–
–
–
4
o
0414
361
414
–
–
–
4
o
0477
414
477
–
–
–
4
o
0590
477
590
–
–
–
4
o
0720
590
720
–
–
–
4
o
0900
720
900
–
–
–
4
o
0930
900
930
u
Control Mode Selection
gives an overview of the U1000 control modes and their various features.
Table 1.2 Control Modes and Features
Motor Type
Induction Motors
Permanent Magnet Motors
Comments
Control Mode
V/f
V/f w/PG
OLV
CLV
OLV/PM
AOLV/PM
CLV/PM
–
Parameter Setting
A1-02 = 0
A1-02 = 1
A1-02 = 2
A1-02 = 3
A1-02 = 5
A1-02 = 6
A1-02 = 7
Default Setting is
OLV control
(A1-02 =2)
Basic Description
V/f control
V/f control
using motor
speed feedback
Open Loop
Vector control
Closed Loop
Vector control
Open Loop
Vector control
for PM motors
Open Loop
Vector control
for IPM motors
Closed Loop
Vector control
for PM motors
–
1.2 General Description
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
31
1
Receiving
Summary of Contents for U1000 iQpump Drive
Page 705: ......