H2 Multi-Function Digital Output Settings
H2-
oo
Setting
Function
LCD Display
Description
Page
0
During run
During RUN 1
All Modes
Closed: A Run command is active or voltage is output.
1
Zero speed
Zero Speed
All Modes
Open: Output speed is greater than or equal to the value of E1-09 (Minimum Output
Frequency) or b2-01 (DC Injection Braking Start Frequency).
Closed: Output frequency is less than the value of E1-09 (Minimum Output
Frequency) or b2-01 (DC Injection Braking Start Frequency).
2
Speed agree 1
Fref/Fout Agree1
All Modes
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
set to L4-02).
3
User-set speed agree 1
Fref/Set Agree 1
All Modes
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
hysteresis set to L4-02).
4
Frequency detection 1
Freq Detect 1
All Modes
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
determined by L4-02.
5
Frequency detection 2
Freq Detect 2
All Modes
Closed: Output frequency is greater than or equal to the value in L4-01 with
hysteresis determined by L4-02.
6
Drive ready
Drive Ready
All Modes
Closed: Power up is complete and the drive is ready to accept a Run command.
7
During Power Supply
Voltage Fault
DC Bus Undervolt
All Modes
Closed: One of the following faults will occur: AUv (Power Supply Undervoltage),
Uv (Undervoltage). or Fdv (Power Supply Frequency Fault).
8
During baseblock
(N.O.)
BaseBlk 1
All Modes
Closed: Drive has entered the baseblock state (no output voltage).
9
Frequency reference
source
Ref Source
All Modes
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or
b1-15).
Closed: Digital operator supplies the frequency reference.
A
Run command source
Run Cmd Source
All Modes
Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).
Closed: Digital operator supplies the Run command.
B
Torque detection 1
(N.O.)
Trq Det 1 N.O.
All Modes
Closed: An overtorque or undertorque situation has been detected.
C
Frequency reference
loss
Loss of Ref
All Modes
Closed: Analog frequency reference has been lost.
Frequency reference loss is detected when the frequency reference drops below
10% of the reference within 400 ms.
E
Fault
Fault
All Modes
Closed: Fault occurred (this excludes CPF00 and CPF01).
F
Through mode
Not Used
All Modes
Select this setting when the terminal is not used or when using the terminal in the
pass-through mode.
10
Minor fault
Minor Fault
All Modes
Closed: An alarm has been triggered.
11
Fault reset command
active
Reset Cmd Active
All Modes
Closed: The drive has received a reset command from the multi-function input
terminals or from a serial network, or the RESET key on the digital operator has
been pressed.
12
Timer output
Timer Output
All Modes
Closed: Timer output.
B.9 H Parameters: Multi-Function Terminals
540
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual