Verifying Parameter Changes: Verify Menu
The Verify Menu lists edited parameters from the Programming Mode or as a result of Auto-Tuning. The Verify Menu helps
determine which settings have been changed, and is particularly useful when replacing a drive. If no settings have been changed,
the Verify Menu will read “None”. The Verify Menu also allows users to quickly access and re-edit any parameter settings
that have been changed.
Note:
The Verify Menu will not display parameters from the A1 group (except for A1-02) or E5-01 even if those parameters have been changed
from their default settings.
The following example is a continuation of the steps above. Here, parameter C1-02 is accessed using the Verify Menu, and
is changed again from 10.0 s to 20.0 s.
To check the list of edited parameters:
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
FREF (AI)
Rdy
RSEQ
RREF
FWD
JOG
2.
Press
or
until the display shows the top of the Verify Menu.
- MODE -
PRG
Modified Consts
HELP
DATA
FWD
Modified
X Parameters
3.
Press
to enter the list of parameters that have been edited from their original default
settings.
If parameters other than C1-02 have been changed, use
or
to scroll until C1-02
appears.
C1-02
= 20.0sec
(0.0~6000.0)
“10.0sec”
FWD
- VERIFY -
PRG
Accel Time 1
Rdy
Home
DATA
4.
Press
.
Press
F1
,
F2
,
,
or
to change the setting value.
FWD
C1-01=
0
020.0sec
(0.0~6000.0)
“10.0sec”
- VERIFY - PRG
Accel Time 1
Rdy
5.
Press
to confirm the change.
Entry Accepted
4.3 The Drive and Programming Modes
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
143
4
Start-Up Programming & Operation