u
Three-Phase 400 V Class Drive Models 4
o
0096 to 4
o
0414
Table A.5 Power Ratings (Three-Phase 400 V Class) Continued
Item
Specification
Drive Model
4
o
0096 4
o
0124 4
o
0156 4
o
0180 4
o
0216 4
o
0240 4
o
0302 4
o
0361 4
o
0414
Maximum Applicable Motor
HD Rating
45 (60)
55 (75)
75 (100) 90 (125) 110 (150)
132 (175)
150 (200) 185 (250) 220 (300)
ND Rating
55 (75)
75 (100) 90 (125) 110 (150) 132 (175)
150 (200)
185 (250) 220 (300) 260 (350)
Input/
Output
Rating
Rated Input
Current (A)
HD Rating
70
87
113
142
164
197
218
275
329
ND Rating
87
113
142
164
197
218
275
329
377
Rated Input
Capacity (kVA)
HD Rating
64
80
103
130
150
180
200
251
300
ND Rating
80
103
130
150
180
200
251
300
344
Rated Output
HD Rating
77
96
124
156
180
216
240
302
361
ND Rating
96
124
156
180
216
240
302
361
414
Overload Tolerance
HD Rating: 150% of rated output current for 60 s
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
4 kHz
(User adjustable up
to 8 kHz. Derating
may be required.)
4 kHz
(User adjustable up
to 6 kHz. Derating
may be required.)
4 kHz
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
400 Hz (User-adjustable)
Power
Supply
Rated Voltage
Rated Frequency
Three-phase 4A
oooo
and 4P
oooo
380 to 500 Vac 50/60 Hz
Three-phase 4E
oooo
and 4W
oooo
380 to 480 Vac 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
Allowable Phase Power Supply
Voltage Unbalance
2% or less
5% or less (IEEE519 compliant)
Input Power Factor
0.98 or more (During rated operation)
connections, and power supply impedance.
<3> Rated input capacity is calculated with a power line voltage of 480 V × 1.1.
<4> The rated output current of the drive should be equal to or greater than the motor rated current.
<5> Carrier frequency is set to 4 kHz. Current derating is required to raise the carrier frequency.
<6> Commercial power mode results in near zero input harmonics. Existing power conditions and operation mode can affect input harmonics.
A.2 Power Ratings
480
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Summary of Contents for U1000 iQpump Drive