WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Check all mechanical or electrical connections
thoroughly before making any setting changes to o2-01 and b1-07.
lists the setting combinations for o2-01 and b1-07.
Table 5.43 LO/RE Key and b1-07
o2-01
b1-07
Switch from LOCAL to REMOTE
Switch from REMOTE to LOCAL
0
0
Not possible
Not possible
1
Not possible
Not possible
1
0
Will not run until a new Run command is
entered.
Run not possible
1
If a Run command is entered, the drive will start
running as soon as the LO/RE key is pushed to
change from LOCAL to REMOTE.
Run not possible
n
o2-02: STOP Key Function Selection
Determines if the STOP key on the digital operator will stop drive operation when the drive is controlled from a remote source
(i.e., not from digital operator).
No.
Name
Setting Range
Default
o2-02
STOP Key Function Selection
0, 1
1
Setting 0: Disabled
Setting 1: Enabled
The STOP key will terminate drive operation even if the Run command source is not assigned to the digital operator. Cycle
the Run command to restart the drive if the drive has been stopped by pressing the STOP key.
n
o2-03: User Parameter Default Value
After completely setting up drive parameters, save the values as user-set defaults with parameter o2-03. After saving the values,
parameter A1-03 (Initialize Parameters) will offer the choice of "1110: User Initialize". Selecting 1110 resets all parameters
to the user-set default values.
Refer to A1-03: Initialize Parameters on page 181
for details on drive initialization.
No.
Name
Setting Range
Default
o2-03
User Parameter Default Value
0 to 2
0
Setting 0: No Change (Awaiting Command)
Setting 1: Set User Initialize Values
The current parameter settings are saved as user-set default for a later User Initialization. Setting o2-03 to 1 and pressing the
ENTER key saves the values and returns the display to 0.
Setting 2: Clear User Initialize Values
All user-set defaults for “User Initialize” are cleared. Setting o2-03 to 2 and pressing the ENTER key erases the values and
returns the display to 0.
n
o2-04: Drive Model Selection
Set this parameter when replacing the control board or the terminal board.
Refer to Defaults by Drive Model and Duty Rating
for information on drive model selection.
NOTICE: Drive performance will suffer and protective functions will not operate properly if the correct drive capacity is not set to o2-04.
No.
Name
Setting Range
Default
o2-04
Drive Model Selection
-
Determined by
drive capacity
Note:
Change o2-04 setting only when necessary.
n
o2-05: Frequency Reference Setting Method Selection
Determines if the ENTER key must be pressed after changing the frequency reference using the digital operator while in the
Drive Mode.
5.10 o: Operator Related Settings
346
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual