n
n8-66: Output Voltage Limit Output Filter Time Constant (for PM Motors)
There is normally no need to change this parameter from the default value.
Note:
1.
This parameter is only available in OLV/PM, AOLV/PM, and CLV/PM.
2.
This parameter is available in drive software versions PRG: 1017 and later.
No.
Name
Setting Range
Default
n8-66
Output Voltage Limit Output Filter Time Constant (for PM Motors)
0.000 to 5.000 s
0.001 s
n
n8-69: Speed Calculation Gain
Sets the proportional gain for Phase Locked Loop (PLL) control of an extended observer.
There is normally no need to change this parameter from the default value.
No.
Name
Setting Range
Default
n8-69
Speed Calculation Gain
0.00 to 20.00
1.00
n
n8-72: Speed Estimation Method Selection
Sets the method of the speed estimation. There is normally no need to change this parameter from the default value.
No.
Name
Setting Range
Default
n8-72
Speed Estimation Method Selection
0, 1
1
Setting 0: Conventional Method
Setting 1: 1000-Series Method
n
n8-84: Initial Polarity Estimation Timeout Current
Sets the current to determine polarity for the initial polarity calculation as a percentage of the motor rated current.
Set the value in % unit (E5-03 = 100%)
Note:
1.
This parameter is only available in AOLV/PM and CLV/PM.
2.
If operating in AOLV/PM (A1-02 = 6) or CLV/PM (A1-02 = 7), the drive determines motor polarity by performing initial polarity
estimation when it starts the motor (this is done only the first time the motor is started when using CLV/PM).
The drive may begin operating in the wrong direction if it determines motor polarity incorrectly as the opposite direction of the Run
command.
Monitor U6-57 displays the deviation from the integrated current, making it possible to see if initial polarity estimation has successfully
determined the motor polarity.
3.
If an “Si” value is listed on a Yaskawa motor nameplate, set n8-84 to “Si” value x 2.
No.
Name
Setting Range
Default
n8-84
Initial Polarity Estimation Timeout Current
0 to 150%
100%
5.9 n: Special Adjustments
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
343
5
Parameter Details