Setting
Function
Page
8
During Baseblock (N.O.)
9
Frequency Reference Source
A
Run Command Source
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
E
Fault
F
Through Mode
10
Minor Fault
11
Fault Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
During Reverse
1B
During Baseblock (N.C.)
1C
Motor 2 Selection
1D
During regeneration
1E
Restart Enabled
1F
Motor Overload Alarm (oL1)
20
Drive Overheat Pre-Alarm (oH)
22
Mechanical Weakening Detection
2F
Maintenance Period
Setting
Function
Page
30
During Torque Limit
31
During Speed Limit
32
During Speed Limit in Torque Control
33
Zero Servo Complete
37
During Frequency Output
38
Drive Enabled
39
Power Consumption Pulse Output
3A
Regenerated Power Pulse Output
3C
LOCAL/REMOTE Status
3D
During Speed Search
3E
PID Feedback Low
3F
PID Feedback High
4C
During Fast Stop
4D
oH Pre-Alarm Time Limit
60
Internal Cooling Fan Alarm
61
Rotor Position Detection Completed
62
MEMOBUS Register 1 (Selected with H2-07 and
H2-08)
63
MEMOBUS Register 2 (Selected with H2-09 and
H2-10)
64
During Commercial Power Operation
90
DriveWorksEZ Digital Output 1
91
DriveWorksEZ Digital Output 2
92
DriveWorksEZ Digital Output 3
100 to 192 Functions 0 to 92 with Inverse Output
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status
Description
Open
Drive is stopped.
Closed
A Run command is input or the drive is in deceleration or DC injection.
ON
ON
OFF
OFF
ON
OFF
Run command
Baseblock
command
Output
frequency
During Run
Figure 5.66 During Run Time Chart
Setting 1: Zero Speed
Terminal closes when the output frequency or motor speed (CLV, CLV/PM) becomes less than or equal to the minimum output
frequency set to E1-09 or b2-01.
5.7 H: Terminal Functions
288
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual