H1 Multi-Function Digital Input Selections
H1-
oo
Setting
Function
LCD Display
Description
Page
11
Down command
Down Command 1
All Modes
The drive accelerates when the Up command terminal closes, and decelerates when
the Down command closes. When both terminals are closed or both are open, the
drive holds the frequency reference. The Up and Down commands must always
be used in conjunction with one another.
12
Forward Jog
Forward Jog
All Modes
Closed: Runs forward at the Jog frequency d1-17.
13
Reverse Jog
Reverse Jog
All Modes
Closed: Runs reverse at the Jog frequency d1-17.
14
Fault reset
Fault Reset
All Modes
Closed: Resets faults if the cause is cleared and the Run command is removed.
15
Fast Stop (N.O.)
Fast-Stop N.O.
All Modes
Closed: Decelerates at the Fast Stop time set to C1-09.
16
Motor 2 selection
Motor 2 Select
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
V/f w PG
OLV
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
V/f w PG
OLV
CLV
Open: Motor 1 (E1-
oo
, E2-
oo
)
Closed: Motor 2 (E3-
oo
, E4-
oo
)
17
Fast Stop (N.C.)
Fast-Stop N.C.
All Modes
Open: Decelerates to stop at the Fast Stop time set to C1-09.
18
Timer function input
Timer function
All Modes
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction
with the timer function output (H2-
oo
= 12).
19
PID disable
PID Disable
All Modes
Open: PID control enabled
Closed: PID control disabled
1A
Accel/decel time
selection 2
Multi-Acc/Dec 2
All Modes
Used in conjunction with an input terminal set for “Accel/decel time selection 1”
(H1-
oo
= 7), and allows the drive to switch between accel/decel times 3 and 4.
1B
Program lockout
Program Lockout
All Modes
Open: Parameters cannot be edited (except for U1-01 if the reference source is
assigned to the digital operator).
Closed: Parameters can be edited and saved.
1E
Reference sample hold
Ref Sample Hold
All Modes
Closed: Samples the analog frequency reference and operates the drive at that
speed.
B.9 H Parameters: Multi-Function Terminals
536
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual