Drive
Model
Terminal
For USA and Canada
For South America
Screw
Size
Tightening
Torque
N·m (lb.in.)
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
4
o
R/L1, S/L2, T/L3
95 × 4P
(3/0 × 4P)
150 × 2P
70 to 150 × 4P
(300 × 2P
2/0 to 300 × 4P)
120 × 2P
(250 × 2P)
95 to 150 × 2P
(4/0 to 300 × 2P)
M12
31.4 to 39.2
(278 to 347)
U/T1, V/T2, W/T3
95 × 4P
(3/0 × 4P)
150 × 2P
70 to 150 × 4P
(300 × 2P
2/0 to 300 × 4P)
120 × 2P
(250 × 2P)
95 to 150 × 2P
(4/0 to 300 × 2P)
M12
31.4 to 39.2
(278 to 347)
50
(1/0)
50 to 150
(1/0 to 300)
120
(250)
95 to 150
(4/0 to 300)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
4
o
R/L1, S/L2, T/L3
120 × 4P
(250 × 4P)
95 to 150 × 4P
(3/0 to 300 × 4P)
95 × 4P
(4/0 × 4P)
120 to 150 × 2P
70 to 150 × 4P
(250 to 300 × 2P
2/0 to 300 × 4P)
M12
31.4 to 39.2
(278 to 347)
U/T1, V/T2, W/T3
120 × 4P
(250 × 4P)
95 to 150 × 4P
(3/0 to 300 × 4P)
95 × 4P
(4/0 × 4P)
120 to 150 × 2P
70 to 150 × 4P
(250 to 300 × 2P
2/0 to 300 × 4P)
M12
31.4 to 39.2
(278 to 347)
70
(2/0)
70 to 150
(2/0 to 300)
95 × 2P
(4/0 × 2P)
120 to 150
95 to 150 × 2P
(250 to 300
4/0 to 300 × 2P)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
4
o
X, Y, Z
150 × 4P
(300 × 4P)
120 to 150 × 4P
(250 to 300 × 4P)
120 × 4P
(250 × 4P)
95 to 150 × 4P
(4/0 to 300 × 4P)
M12
31.4 to 39.2
(278 to 347)
X1, Y1, Z1
50
(1/0)
50 to 70
(1/0 to 2/0)
35
(1)
35 to 50
(1 to 1/0)
M8
5.4 to 6.0
(47.8 to 53.0)
U/T1, V/T2, W/T3
150 × 4P
(300 × 4P)
120 to 150 × 4P
(250 to 300 × 4P)
120 × 4P
(250 × 4P)
95 to 150 × 4P
(4/0 to 300 × 4P)
M12
31.4 to 39.2
(278 to 347)
95
(3/0)
95 to 150
(3/0 to 300)
120 × 2P
(250 × 2P)
95 to 150 × 2P
(4/0 to 300 × 2P)
M12
31.4 to 39.2
(278 to 347)
r1, s1, t1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
p1, n1
2.5
(14)
2.5 to 16
(14 to 6)
2.5
(14)
2.5 to 16
(14 to 6)
M5
2.0 to 2.5
(17.4 to 21.7)
p2, n2
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
4
o
X, Y, Z
95 × 8P
(4/0 × 8P)
150 × 4P
70 to 150 × 8P
(300 × 4P
2/0 to 300 × 8P)
150 × 4P
(300 × 4P)
120 to 150 × 4P
(250 to 300 × 4P)
M12
31.4 to 39.2
(278 to 347)
X1, Y1, Z1
50
(1/0)
50 to 70
(1/0 to 2/0)
35
(1)
35 to 50
(1 to 1/0)
M8
5.4 to 6.0
(47.8 to 53.0)
U/T1, V/T2, W/T3
95 × 8P
(4/0 × 8P)
150 × 4P
70 to 150 × 8P
(300 × 4P
2/0 to 300 × 8P)
150 × 4P
(300 × 4P)
120 to 150 × 4P
(250 to 300 × 4P)
M12
31.4 to 39.2
(278 to 347)
95
(4/0)
95 to 150
(4/0 to 300)
150 × 2P
(300 × 2P)
120 to 150 × 2P
(250 to 300 × 2P)
M12
31.4 to 39.2
(278 to 347)
r1, s1, t1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
p1, n1
2.5
(14)
2.5 to 16
(14 to 6)
2.5
(14)
2.5 to 16
(14 to 6)
M5
2.0 to 2.5
(17.4 to 21.7)
p2, n2
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
3.8 Main Circuit Wiring
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
103
3
Electrical Installation
Summary of Contents for U1000 iQpump Drive
Page 705: ......