2.2 Mechanical Installation
This section outlines specifications, procedures, and the environment for proper mechanical installation of the drive and
harmonic filter module.
u
Installation Environment
Install the drive and harmonic filter module in an environment matching the specifications in
prolong optimum performance life.
n
Drive Models 2
o
0028 to 2
o
0248 and 4
o
0011 to 4
o
0930
Table 2.1 Drive Installation Environment
Environment
Conditions
Installation Area
Indoors
Ambient Temperature
IP00/Open Type enclosure: -10 °C to +50 °C (14 °F to 122 °F)
IP20/ UL Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)
Drive reliability improves in environments without wide temperature fluctuations.
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air
temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
Humidity
95% RH or less and free of condensation
Storage Temperature
-20 °C to +60 °C (-4 °F to +104 °F)
Surrounding Area
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
Altitude
1000 m (3281 ft.) or lower, up to 3000 m (9843 ft.) with derating.
Refer to Drive Derating Data on page 486
for details.
Vibration
10 to 20 Hz: 9.8 m/s
2
(4
o
0477 to 4
o
0930: 5.9 m/s
2
)
20 to 55 Hz: 5.9 m/s
2
(2
o
0104 to 2
o
0248, 4
o
0096 to 4
o
0930: 2.0 m/s
2
)
Orientation
Install the drive vertically to maintain maximum cooling effects.
NOTICE: Avoid placing peripheral devices, transformers, or other electronics near the drive, as the noise created can lead to erroneous
operation. Take proper steps to shield the drive from noise if such devices must be used in close proximity.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to comply
could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary cover before
start-up, as the cover will reduce ventilation and cause overheat.
2.2 Mechanical Installation
58
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual