No.
Name
Unit
Default Settings
–
Drive Model
–
4
o
0361
4
o
0414
4
o
0477
4
o
0590
C6-01
Drive Duty Selection
–
HD
ND
HD
ND
HD
ND
HD
ND
o2-04
Drive Model Selection
Hex.
A9
AA
AC
AD
E2-11
(E4-11)
Motor Rated Output
kW
(HP)
185
(250)
220
(300)
220
(300)
260
(350)
260
(350)
300
(400)
300
(400)
375
(500)
E5-01
Motor Code Selection (for PM Motors)
Hex.
124A
124A
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
Momentary Power Loss Ride-Thru Time
s
1.8
1.9
1.9
2
2
2.1
2.1
2.1
L2-03
Momentary Power Loss Minimum
Baseblock Time
s
1
1
1
1
1.8
2.0
2.0
2.0
L2-04
Momentary Power Loss Voltage Recovery
Time
s
300
300
300
300
300
300
300
300
L2-21
Low Input Voltage Detection Level
V
300
300
300
300
300
300
300
300
L8-02
Overheat Alarm Level
°C
130
130
130
130
130
130
130
130
L8-35
Installation Method Selection
–
0
0
0
0
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
30
30
100
100
100
100
100
100
n5-02
Motor Acceleration Time
s
0.777
0.864
0.864
0.91
0.91
1.392
1.392
1.392
Table B.17 400 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
No.
Name
Unit
Default Settings
–
Drive Model
–
4
o
0720
4
o
0900
4
o
0930
C6-01
Drive Duty Selection
–
HD
ND
HD
ND
HD
ND
o2-04
Drive Model Selection
Hex.
AE
AF
B0
E2-11 (E4-11)
Motor Rated Output
kW
(HP)
300 (400) 375 (500) 375 (500) 450 (600) 450 (600)
500
b3-04
V/f Gain during Speed Search
%
60
60
60
60
60
60
b3-06
Output Current 1 during Speed Search
–
0.7
0.7
0.7
0.7
0.7
0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.8
0.8
0.8
0.8
0.8
0.8
b8-03
Energy Saving Control Filter Time Constant
s
2
2
2
2
2
2
b8-04
Energy Saving Coefficient Value
–
21.76
23.84
23.84
21.4
21.4
20.26
C5-17 (C5-37) Motor Inertia
kgm
2
11
12
12
13
13
14
C6-02
Carrier Frequency Selection
–
0
0
0
0
0
0
E2-01 (E4-01)
Motor Rated Current
A
500
650
650
800
800
900
E2-02 (E4-02)
Motor Rated Slip
Hz
1.25
1
1
1
1
0.9
E2-03 (E4-03)
Motor No-Load Current
A
130
130
130
160
160
180
E2-05 (E4-05)
Motor Line-to-Line Resistance
Ω
0.014
0.012
12.000 mΩ 10.000 mΩ 10.000 mΩ 9.000 mΩ
E2-06 (E4-06)
Motor Leakage Inductance
%
20
20
20
20
20
20
E2-10 (E4-10)
Motor Iron Loss for Torque Compensation
W
4700
5560
5560
7060
7060
7833
E5-01
Motor Code Selection (for PM Motors)
Hex.
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
Momentary Power Loss Ride-Thru Time
s
2.1
2.3
2.3
2.8
2.8
3.1
L2-03
Momentary Power Loss Minimum Baseblock Time
s
2
2.2
2.2
2.6
2.6
3
L2-04
Momentary Power Loss Voltage Recovery Time
s
300
300
300
300
300
300
L2-21
Low Input Voltage Detection Level
V
300
300
300
300
300
300
L8-02
Overheat Alarm Level
°C
135
135
135
135
135
135
L8-35
Installation Method Selection
–
0
0
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
100
100
100
100
100
100
n5-02
Motor Acceleration Time
s
1.392
1.667
1.667
2
2
2.222
B.18 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
593
B
Parameter List
Summary of Contents for U1000 iQpump Drive
Page 705: ......