4.8 No-Load Operation Test Run
u
No-Load Operation Test Run
This section explains how to operate the drive with the motor decoupled from the load during a test run.
n
Before Starting the Motor
Check the following items before operation:
• Ensure the area around the motor is safe.
• Ensure external emergency stop circuitry is working properly and other safety precautions have been taken.
n
During Operation
Check the following items during operation:
• The motor should rotate smoothly (i.e., no abnormal noise or oscillation).
• The motor should accelerate and decelerate smoothly.
n
No-Load Operation Instructions
The following example illustrates a test run procedure using the digital operator.
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
FREF (AI)
Rdy
RSEQ
RREF
FWD
JOG
2.
Press
to select LOCAL. The LO/RE light will turn on.
LO
RE
F2
F1
ESC
RUN
STOP
ENTER
RESET
ALM
DIGITAL OPERATOR JVOP-180
Off
On
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
FREF (OPR)
Rdy
JOG
FWD
FWD/REV
LSEQ
LREF
3.
Set the frequency reference to 6 Hz.
Refer to Setting the Frequency Reference while in
–
–
4.
Press
to give the drive a Run command. RUN will light and the motor will rotate
at 6 Hz.
LO
RE
F2
F1
ESC
RUN
STOP
ENTER
RESET
ALM
DIGITAL OPERATOR JVOP-180
RUN
RUN
Off
On
- MODE -
U1-01= 6.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
FREF (OPR)
Rdy
JOG
FWD
FWD/REV
LSEQ
LREF
5.
Ensure the motor is rotating in the correct direction and that no faults or alarms occur.
Motor
Forward
6.
If there is no error in step 4, increase the frequency reference.
Frequency Reference while in the Drive Mode on page 141
increments of 10 Hz, verifying smooth operation at all speeds. For each frequency, check
the drive output current using monitor U1-03. The current should be well below the motor
rated current.
–
–
4.8 No-Load Operation Test Run
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual