65
By selecting the
24-hour
mode is useful for sensors or applications where the customer wants
to know about any changes in input status - regardless of whether the alarm status is active.
Thus, in the non-armed mode - 24 hours - all input changes are detected and signaled.
For sabotage detection (sensor tamper protection) the
IxEOL
parameter can be used for the
given input, EOL (
end of line
) resistor can be configured for open detection (tamper detection
function). This will always generate an alarm if it is
Enabled
!
In case of wiring tamper or sensor sabotage, the T2 point of the sensor must be connected to
the “
-
” terminal of the
Easy2S
®
input, the T1 terminal of the sensor to the NC wire, and the C
wireto the positive (+) wire terminal of the devic
’s
input.
Important!
It is highly important to turn off the
Bypass
feature for the inputs, that the
events can be signaled by the system.
Choose the Bypass tab on the top of the screen at right then choose the
„Easy 2 inputs”
option.
Then the application loads the currents inputs status and settings for each inputs. Push the
OFF
button for each input’s
IxBypass
value.