8
In voltage input operation mode, the input lines can be activated with 5-24V DC voltage, in
opposite way these are inactive.
The proper operation mode must be configured as well with the
EasyTerm
application.
The inputs can be configured seperately - to operate as a voltage or contact mode for the related
input. These settings can be installed by the closing the related jumper pairs, besides the input
terminal block
–
according to the input line nr. titles.
Jumperable input modes (with the JP1, JP2 jumpers):
•
Contact mode
o
The input line jumper pairs - approach from the connector side (lower two
pins must be closed)
o
The ground point of the input lines (-) are common
o
The wiring of input lines has independent polarity
BEMENETEK
(IN1, IN2)
KIMENET
(OUT)
JP2
(IN2)
JP1
(IN1)