10
Signal levels:
•
Input high signal level:
2-24V
•
Input low signal level:
0-1V
•
Current in active status (for the
Easy2S
inputs):
0.33mA
•
Current in active status (for the further IO-expansion board inputs):
1-12mA
When the input were activated (IN1, IN2) the
INx
titled LEDs are signing the active (closed)
status during the operation, with the proper light and colour. See
LED signals
part.
In case of using the
IO
-expander board, further 6 pcs of inputs are available (IN3..IN8), which
have the same operation and configuration possibility as listed here above.
In case of using the
Easy2 IO
-expander board, further 6pcs inputs are available
(IN3..IN8). Their operation and configuration are the same as we described for the
main board. The IO-expnader inputs can be activated with 2-32V voltage.
◼
Connecting the relay output
One switchable output device can be connected to the relay output (
OUT
) of the mainboard),
according to the next figure. Connect the blanked cable wire pair to the
OUT
title output line
’s
terminal block (by sliding the companion piece and inserting the stripped wire pair, then fixing
the screws).
Through the relay output a 2A - 120VAC or 1A
- 24VDC voltage can be switched. When
activating the output line (
OUT
), the
OUT
LED
–
beside the output - indicates the active
(closed) position with the appropriate
color/light - during the operation.
Attention!
Always switch off power supply before the wiring!
Check that the metal parts of the connected wires are not touch to each other!
The Easy2 IO
-
expander
provides further 3 outputs (OUT2..OUT4). Their operation and
configuration is the same as we described.