176 I/O Modules
WAGO-I/O-SYSTEM 750
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
Table 132: Output Process Image Counter Modules
Output process image
Instance
Byte designation
Remark
n
C0
Control byte of counter 1
D0
Counter setting value counter 1
D1
n+1
C1
Control byte of counter 2
D2
Counter setting value counter 2
D3
These specialty modules represent 2 x 3 bytes and occupy 2 instances in class
(0x68).
SSI transmitter interface
750-630 (and all versions /000-001, -002, -006, -008, -009, -011, -012, -013)
In the input and output process image, SSI transmitter interface modules occupy 4
data bytes. A total of 4 bytes are occupied in the process image.
Table 133: Input Process Image, SSI Transmitter Interface Modules
Input Process Image
Instance
Byte designation
Remark
n
D0
Data bytes
D1
n+1
D2
D3
These specialty modules represent 2 x 2 bytes and occupy 2 instances in class
(0x67).
SSI transmitter interface
750-630/000-004, -005, -007
In the input process image, SSI transmitter interface modules with status occupy 5
bytes of user data: 4 data bytes and one additional status byte. A total of 6 bytes
are occupied in the process image.
Table 134: Input Process Image, SSI Transmitter Interface Modules
Input Process Image
Instance
Byte designation
Remark
n
S
Status byte
-
not used
D0
Data bytes
D1
D2
D3
These specialty modules represent 1 x 6 bytes and occupy 1 instance in class
(0x67).