WAGO-I/O-SYSTEM 750
I/O Modules 183
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
Table 151: Output Process Image, Radio Receiver I/O Module
Output process image
Instance
Byte designation
Remark
n
C
Control byte
-
not used
n+1
-
-
These specialty modules represent 2 x 2 bytes and occupy 2 instances in class
(0x67) and 2 instances in class (0x68).
MP Bus Master Module
750-643
In the input and output process image, the MP bus master module occupies 8
bytes of user data: 6 data bytes and 2 additional control/status bytes. 8 bytes are
occupied in the process image.
Table 152: Input/Output Process Image, MP Bus Master Module
Input/Output Process Image
Instance
Byte designation
Remark
n
C0/S0
Control/status byte
C1/S1
Additional control/status byte
D0
Data bytes
D1
D2
D3
D4
D5
These specialty modules represent 1 x 8 bytes and occupy 1 instance in class
(0x67) and 1 instance in class (0x68).
Bluetooth
®
RF transceiver
750-644
The length of the process image of the
Bluetooth
®
I/O module can be adjusted to a
fixed size of 12, 24 or 48 Byte.
It consists of one control byte (input) or one status byte (output), one empty byte,
one 6-, 12- or 18-byte overlayable mailbox (mode 2) and the
Bluetooth
®
process
data with a size of 4 to 46 bytes.
The
Bluetooth
®
I/O module uses between 12 to 48 bytes in the process image. The
size of the input and output process images are always the same.
The first byte contains the control/status byte; the second contains an empty byte.