Programming the PFC Using WAGO-I/O-PRO
WAGO-I/O-SYSTEM 750
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
9.1
Configuring the Fieldbus Controller using the I/O
Configurator
The I/O Configurator is a plug-in integrated into WAGO-I/O-
PRO
used to
determine addresses for I/O modules at a fieldbus controller.
1.
In the left half of the screen for the WAGO-I/O-
PRO
interface, select the
tab
Resources
.
2.
To start the I/O Configurator, double-click in the tree structure on
Control
system configuration
.
3.
Expand the branch
Hardware configuration
in the tree structure.
4.
Right-click on the entry
K-Bus
and then select
Edit
in the context menu.
5.
In the “Configuration” window that then opens, click on
Add
to open the
module selection window.
6.
Select the I/O module you wish to add from the module catalog and attach it
to the end of the internal data bus structure by clicking on
[>>]
and
OK
.
7.
Position all of the required I/O modules in their correct order until this
arrangement matches the configuration of the physical node.
Arrange the tree structure in the hardware configuration in the same manner.
Include all I/O modules which supply or receive data.
If you access your fieldbus controller online, you can use the
[Start WAGO-I/O-
CHECK and scan]
button in the “Configuration” window to read in the
physically linked fieldbus controllers with the series-connected I/O modules and
display all of the components.
The internal data bus structure in the WAGO I/O Configurator must match
the physical node structure!
The number of I/O modules that send or receive data must correspond to the
existing hardware (except for supply modules, copying modules or end modules,
for example). For the number of input and output bits or bytes of the individual
I/O modules please refer to their corresponding descriptions.