8.2
Setting the DeviceNet
™
Station Address and Baud
Rate
1.
Set the required DeviceNet
™
station address (“MAC ID”) using slide
switches 1 … 6 of the DIP switch.
2.
Set the required baud rate using slide switches 7 and 8.
Example:
Setting the station address “MAC ID” 4 (DIP 3 = ON) and baud rate 500 kBaud
(DIP 7 = OFF, DIP 8 = ON).
OFF
Station address
OFF
ON (2² = 4)
OFF
OFF
OFF
OFF
Baud rate
ON
Figure 42: Example of DIP Switch Settings
3.
Then switch the fieldbus controller power supply on.