WAGO-I/O-SYSTEM 750
Fieldbus Communication 155
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
Table 96: Instance 1
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Description
13
specific
get/set
BK_SEL_STO
RED_POLL_C
_PATH
UINT
Power-up value for the receive
path. “Polled I/O” enumeration
for the assembly path, class and
instance for the I/O module
objects.
Notice: Only write values to this
attribute that are also available,
e.g., do not use analog inputs if
only digital input/output
modules are linked.
14
specific
get/set
BK_SEL_STO
RED_COSCY
C_C_PATH
UINT
Power-up value for change of
state and cyclic connection.
Enumeration for the assembly
path, class and instance of the
I/O module objects.
Notice: Only write values to this
attribute that are also available,
e.g., do not use analog inputs if
only digital input/output
modules are linked.
15
specific
get/set
BK_EM_expe
cted_packet_rate
UINT
Defines the default time for the
explicit messaging connection
16
specific
get/set
BK_EM_watc
hdog_timeout_
action
USINT
Defines how
inactivity/watchdog explicit
messaging connection timeouts
are handled
17
specific
get/set
BK_PIO_expe
cted_packet_ra
te
UINT
Defines the default time for the
poll I/O connection
18
specific
get/set
BK_PIO_watc
hdog_timeout_
action
USINT
Defines how
inactivity/watchdog poll
connection timeouts are handled
19
specific
get/set
BK_BS_expec
ted_packet_rat
e
UINT
Defines the default time for the
bit-strobe I/O connection
20
specific
get/set
BK_BS_watch
dog_timeout_a
ction
USINT
Defines how
inactivity/watchdog bit-strobe
I/O connection timeouts
are handled
21
specific
get/set
BK_COS_exp
ected_packet_r
ate
UINT
Defines the default time for the
change of state and cyclic I/O
connection
22
specific
get/set
BK_COS_wat
chdog_timeout
_action
USIN
T
Defines how
inactivity/watchdog change
of state and cyclic I/O
connection timeouts
are handled