WAGO-I/O-SYSTEM 750
Fieldbus Communication 147
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
Instance 1 (Explicit Messaging)
Table 87: Instance 1
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Description
1
Available get
state
USINT
Status of the object
2
required
get
instance_ type
USINT
Displays I/O or messaging
connection
3
required
get
transport-
Class_trigger
USINT
Defines the connection behavior
4
required
get
produced_
connection_
id
UINT
In the CAN identifier field when
transmitting
5
required
get
consumed_
connection_
id
UINT
CAN identifier field
value that denotes the message
that should be transmitted
6
required
get
initial_
comm_
characteristics
USINT
Defines the message groups
across which productions and
consumptions associated with this
connection occur
7
required
get
produced_
connection_
size
UINT
Maximum number of bytes that
can be transmitted via the
connection
8
required
get
consumed_
connection_
size
UINT
Maximum number of bytes that
can be received via this
connection
9
required
get/set
expected_
packet_rate
UINT
Defines the timing of the
connection
10, 11
N/A
get
N/A
N/A
not used
12
required
get
watchdog_
timeout_
action
USINT
Defines how to handle inactivity /
watchdog timeouts
13
required
get
produced_
connection_
path_length
UINT
Number of bytes in
“produced_connection_path”
attribute
14
required
get/set
produced_
connection_
path
Array of
USINT
Specifies application objects,
whose data are generated in this
connection object
15
required
get
consumed_
connection_
path_
length
UINT
Number of bytes in the attribute
“consumed_connection_path”
16
required
get
consumed_
connection_
path
Array of
USINT
Specifies application objects,
whose data are received by this
connection object
17
required
get
production_
inhibi
t_time
USINT
Defines the minimum time
between data transmission