52
Device Description
WAGO-I/O-SYSTEM 750
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
Table 28: Technical Data – Data Contacts
Data contacts
Slide contact, hard gold plated, self-
cleaning
4.5.7
Climatic Environmental Conditions
Table 29: Technical Data – Climatic Environmental Conditions
Operating temperature range
0 °C … 55 °C
Operating temperature range for
components with extended
temperature range (750-xxx/025-xxx)
−20 °C … +60 °C
Storage temperature range
−25 °C … +85 °C
Storage temperature range for
components with extended
temperature range (750-xxx/025-xxx)
−40 °C … +85 °C
Relative humidity
Max. 5 % … 95 % without condensation
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75 %
SO
2
≤
25 ppm
H
2
S
≤
10 ppm
Special conditions
Ensure that additional measures for
components are taken, which are used in
an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
4.5.8
Mechanical Strength acc. to IEC 61131-2
Table 30: Technical Data – Mechanical Strength acc. to IEC 61131-2
Test specification
Frequency range Limit value
IEC 60068-2-6 vibration
5 Hz
≤
f < 9 Hz
1.75 mm amplitude (permanent)
3.5 mm amplitude (short term)
9 Hz
≤
f < 150 Hz 0.5 g (permanent)
1 g (short term)
Note on vibration test:
a) Frequency change: max. 1 octave/minute
b) Vibration direction: 3 axes
IEC 60068-2-27 shock
15 g
Note on shock test:
a) A Type of shock: half sine
b) Shock duration: 11 ms
c) Shock direction: 3x in positive and 3x in negative
direction for each of the three mutually
perpendicular axes of the test specimen
IEC 60068-2-32 free fall
1 m (module in original packing)