WAGO-I/O-SYSTEM 750
Fieldbus Communication 161
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
Instance 1 … 255
Table 104: Instance 1
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Value
Description
1
Depending
on the type
of I/O
module
get
DIPOBJ_
VALUE
BIT
0: off
1: on
Digital output bit
Services
Table 105: Service
Service
Code
Service Name
Description
0x0E
Get_Attribute_Single
Returns the content of a specific attribute
0x10
Set_Attribute_Single
Modifies the content of a specific attribute
11.1.5.2.1.10 Analog Input Point Object (0x67)
Instance 0
Table 106: Instance 0
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Value Description
1
required
get
Revision UINT
1
Revision number of the class
definition for the “Identity
Object”
2
optional
get
Max
instance
UINT
256
Maximum number of
instances of an object
generated at the time in this
class level of the device
Description of Instances
Table 107: Description of Instances
Instance ID Description
1
Reference to the first analog input point
2
Reference to the next analog input point
…
255
Reference to the last possible analog input point