WAGO-I/O-SYSTEM 750
Commissioning
93
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
Figure 51: Parameterization
39. Scroll down to the addresses ID#13 and #ID14.
ID#13 is a pointer to the inputs (default = “4”).
The parameter changes when inputs are mapped for the master. Because
inputs can only be read and not written, this is not required.
ID#14 is a pointer to the outputs (default = “1”).
This parameter changes to point to dynamic mapping of outputs that are
mapped in the “Dynamic Assembly Instance” 100
dec
. (0x64
hex
).
40. Leave the value for ID#13 at the default value of “4”.
For ID#14, enter 25604 decimal to aim the pointer on the “Dynamic
Assembly Output” mapping.
The value “25604” corresponds to hexadecimal notation “0x6404”.
04 (low byte) = Class type
64 (high byte) = 100
dec
instance number
41. Change the value for ID#39. Select “Dynamic created instances are stored
in non-volatile memory” to make sure the configuration for the “Dynamic
Assembly” if the controller loses power.
42. To apply the parameters to the fieldbus controller, select the parameter “All
Values” on the “Parameters” tab in the dialog box on the right.