Device Description
WAGO-I/O-SYSTEM 750
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
4.4.3
DIP Switch
Figure 27: DIP Switch
The DIP switch is used to set the baud rate of the fieldbus controller and to set the
DeviceNet
TM
station address (relating to DeviceNet
TM
, also called “MAC ID”).
Settings are made by moving the slide switches to “ON” or “OFF”.
The position of the individual slide switches only evaluated when turning on the
fieldbus controller, i.e., changes are applied when the power supply for the
fieldbus controller is turned OFF then ON again.
4.4.3.1
Baud Rate Setting
The baud rate is set using slide switches 7 and 8 of the DIP switch. 3 different
baud rates are supported.
Table 20: Setting the Baud Rate via DIP Switch
Baud rate
Slide switch 7
Slide switch 8
125 kBaud (default)
OFF
OFF
250 kBaud
ON
OFF
500 kBaud
OFF
ON
not permitted
ON
ON
Example:
Setting the baud rate to 250 kBaud
-
ON
-
OFF
Figure 28: Example with Baud rate Sent to 250 kBaud