140 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
11.1.5.2.1.4 Assembly Object (0x04)
Instance 0
Table 65: Instance 0
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data
Type
Value
Description
1
required
get
Revision UINT
0x02
Revision number of the class
definition for the “Assembly
Object”
Description of Instances
Table 66: Description of Instances
Instance
ID
Description
1
Reference to process image: Analog/digital output data
2
Reference to process image: Digital output data
3
Reference to process image: Analog output data
4
Reference to process image: Analog/digital input data plus status
5
Reference to process image: Digital input data plus status
6
Reference to process image: Analog input data plus status
7
Reference to process image: Analog/digital input data
8
Reference to process image: Digital input data
9
Reference to process image: Analog input data
10
Reference to the process image that contains the PFC output variables.
11
Reference to the process image that contains the PFC input variables.
12
Reference to process image: Analog/digital input data plus error code
13
Reference to process image: Analog/digital input data plus error code
and error argument
14
Reference to process image: Analog/digital input data plus error code
and error argument, status
Instance 1
Table 67: Instance 1
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data
Type
Description
3
Depending
on the type
of I/O
module
get/set
Process
image
Array of
byte
Process image, collection of all output
data of the I/O modules