96
Programming the PFC Using WAGO-I/O-PRO
WAGO-I/O-SYSTEM 750
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
Log in to use the PLC browser with administrator user data!
To use the PLC browser functionality in WAGO-I/O-
PRO
, log into the PLC
browser with the administrator user data (default user “admin”, password
“wago”). Enter “login admin wago” in the command line of the PLC browser.
Figure 53: Logging Into the PLC Browser
A description of programming using WAGO-I/O-
PRO
is not included in this
manual. The following sections, on the other hand, contain important information
about creating projects in WAGO-I/O-
PRO
and about special modules that you
can use explicitly for programming of the Fieldbus Controller DeviceNet
TM
.
Explanations are also provided as to how the IEC 61131-3 program is transferred
and how suitable communication drivers are loaded.
One WAGO-I/O-PRO-/(CODESYS)-Instance per traget system!
Note that a simultaneous connection of multiple WAGO-I/O-
PRO
/(CODESYS)
Instances on one target system is not possible.
Name Conventions for WAGO-I/O-PRO/(CODESYS) Projects!
Note that you do not use special characters for the name of your
WAGO-I/O-
PRO/
(CODESYS) project and limit the name to a maximum of 8
characters.
This will ensure that not always, in case of the online change function is activated
simultaneously, for each online change event a new TxT file is created, which
contains the paths and the project ID, and that for this additional memory is
consumed. With proper choice of the file name, the TxT file is only overwritten
each time and does not consume additional memory space.