154 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
Table 96: Instance 1
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Description
8
specific
get
CnfLen.
AnalogInp
UINT
Number of input/output bits for
the analog input data words
9
specific
get
CnfLen.
DigitalOut
UINT
Number of input/output bits for
the digital output bits
10
specific
get
CnfLen.
DigitalInp
UINT
Number of input/output bits for
the digital input bits
11
specific
get/set
BK_FAULT_
REACTION
USINT
Enumeration for error handling
0: Stops local input/output
cycles (default)
1: Sets all outputs to 0
2: Does nothing
12
specific
get/set
BK_SEL_
STORED_POL
L_P_PATH
UINT
Power-up value for send path.
“Polled I/O” enumeration for the
assembly path, class and
instance for the object path.
(Notice:
e.g., do not choose analog inputs
if only digital input modules on
the node)
4: Analog/digital input data plus
status
5: Digital input data plus status
6: Analog input data plus status
7: Analog/digital input data
8: Digital input data
9: Analog input data
12: Analog/digital input data
plus
BK_LED_ERR_CODE (C 100,
I 1, A45)
13: Analog/digital input data
plus
BK_LED_ERR_CODE (C 100,
I 1, A45) plus
BK_LED_ERR_ARG (C 100, I
1, A46)
14: Analog/digital input data
plus
BK_LED_ERR_CODE (C 100,
I 1, A45) plus
BK_LED_ERR_ARG (C 100, I
1, A46) plus
Status (C 100, I 1 A 5) plus
DNS_i_Trmnldia
(C 100, I 1, A6) plus
BK_DIAG_VALUE
(C 100, I 1, A47)