WAGO-I/O-SYSTEM 750
Programming the PFC Using WAGO-I/O-PRO
97
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
Additional Information:
For a detailed description of using the software, refer to the manual for the
“WAGO-I/O-
PRO
”. This manual is located in the Internet under
1.
Start the programming tool at
Start \ Programs \ WAGO-I/O-PRO
.
2.
Under
File
/
New
create a new project
A dialog window then appears on which you can set the target system for
programming.
Figure 54: Dialog Window for Target System Settings
3.
Select the Fieldbus Controller DeviceNet
TM
750-806 by entering
WAGO_750-806
and then click [
OK]
.
4.
In the dialog window that appears select the program type (AWL, KOP,
FUP, AS, ST or CFC).
To ensure that you can access all I/O module data properly in your new project,
first compile the I/O module configuration based on the existing fieldbus node
hardware and map it in the configuration file “EA-config.xml”.
As described below, this file can be generated via configuration using the WAGO
I/O Configurator.