WAGO-I/O-SYSTEM 750
Programming the PFC Using WAGO-I/O-PRO 105
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
9.4.1
Enabling/Disabling System Events
1.
Open the register
resources > task configuration > system events
in
WAGO-I/O-
PRO
(see the following Figure).
2.
In order to call up a module via an event, activate the entries by setting a
hatch mark in the respective control boxes.
3.
Disable the control boxes by removing the hatch marks through a mouse
click.
Figure 57: Enabling/Disabling System Events
Only use global variables and functions (Fun)!
Note that the fetch of function blocks (FB) such as Timer modules , or the fetch of
blocking functions such as file operations can lead to a malfunction of the system.
Therefore use in system events exclusively Global variables and functions (Fun).
Additional Information:
Allocation of the system events to the specific modules to be called up is clarified
in the manual for the programming tool WAGO-I/O-
PRO
in the Internet under