WAGO-I/O-SYSTEM 750
Fieldbus Communication 137
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
11.1.5.2.1 Object Classes
Defined object classes:
Table 58: Object Classes
Object
Class
Instance
Description
Identity
0x01
1
“Device type”, “Vendor ID”, serial
number, etc.
Message Router
0x02
1
Routes explicit messages
DeviceNet
0x03
1
Maintains the physical link to the
DeviceNet
TM
network.
Allocates/deallocates “Master/Slave
Connection Set”
Assembly
0x04
9
Allows data transmission of different
objects over a single connection, by
combining attributes of different objects
10, 11
Additional assembly as reference to the
process image that contains the PFC
input/output variables
100, 101
Additional dynamic assembly
Connection class
0x05
3
Allows forwarding of explicit messages
Acknowledge handler
0x2B
1
Coordinates receipt of message
confirmations. Communicates with the
application object
Defines “Acknowledge reception”,
“Acknowledge timeouts” and
“Production retry limit”
Coupler configuration object
0x64
1
Device configuration
Discrete input point
0x65
0 ... 255
Digital input channel objects
Discrete output point
0x66
0 ... 255
Digital output channel objects
Analog input point
0x67
0 ... 255
Analog input channel objects
Analog output point
0x68
0 ... 255
Analog output channel objects
Module configuration
0x80
1…65
Description of connected I/O modules
Input Fieldbus Variable USINT
0xA0
1 … 255
PFC Input Variables
Input Fieldbus Variable USINT
0xA1
256 … 510
PFC Input Variables
Input Fieldbus Variable USINT
0xA2
511 … 512
PFC Input Variables
Input Fieldbus Variable UINT
0xA6
1 … 255
PFC Input Variables
Input Fieldbus Variable UINT
0xA7
256
PFC Input Variables
Output Fieldbus Variable UINT
0xA8
1 … 255
PFC Output Variables
Output Fieldbus Variable UINT
0xA9
256
PFC Output Variables
Input Fieldbus Variable UDINT
0xAA 1 … 128
PFC Input Variables
Input Fieldbus Variable UDINT
0xAB
1 … 128
PFC Input Variables
Starts with 2 bytes offset because the
ranges overlap: Class 166 / Instance 2
and 3 (UINT) = Class 171 / Instance 1
(UDINT), etc.
Output Fieldbus Variable UDINT 0xAC
1 … 128
PFC Output Variables
Output Fieldbus Variable UDINT 0xAD 1 … 128
PFC output variables
Starts with 2 bytes offset because the
ranges overlap:
Class 168 / Instance 2 and 3 (UINT) =
Class 173 / Instance 1 (UDINT), etc.