WAGO-I/O-SYSTEM 750
Commissioning
91
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
The [ENTER] closes the dialog window!
Do not click
[ENTER]
because the dialog window closes and has to be opened
again.
30. Click the
[Execute]
button to create the instance for the dynamic assembly.
If the instance is created successfully, the fieldbus node sends instance
number “64 00” (hexadecimal notation).
Figure 49: Creating an Instance for Dynamic Assembly
31. If an error occurs, an error message appears: In this case, check the entries
for Class, Instance and Attribute, the DeviceNet™ connection and
configuration.
32. Select the “Set Single Attribute” service in the “Description” dialog box and
enter the following values in the dialog boxes for the “Object Address”:
•
“Class”
“4”
•
“Instance”
“64” (64
hex
= 100
dec
)
•
“Attribute”
“2”
33. Click in the “Data sent to the device” dialog box and enter the following
values in hexadecimal notation:
10 00 06 00 20 A6 24 01 30 01 10 00 06 00 20 A6 24 02 30 01
The path is written with: