90
Commissioning
WAGO-I/O-SYSTEM 750
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
26. Then click the
Class Instance Editor...
menu item in the “Device” menu.
Figure 47: Opening the “Class Instance Editor”
A window opens with the following warning:
Figure 48: Warning
Select a uniform number format!
The editor changes parameters in the fieldbus controller. Therefore, consistently
enter all data as hexadecimal or decimal.
If the number format of the data is not uniform, it can lead to data loss or cause
the fieldbus controller to fail completely.
28. Click
[Yes]
to confirm the warning.
The “Class Instance Editor” dialog window appears.
29. Select the “Create” service in the "Description" dialog box and enter the
following values in the dialog boxes for the "Object Address":
•
“Class”
“4”
•
“Instance”
“0”
•
“Attribute”
“1”