156 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
Table 96: Instance 1
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Description
23
specific
get/set
BK_BOI
USIN
T
Defines the default value for
BIO (Obj. 0x03 Inst.1,
Att.3.) It handles the CAN-
Bus-Off situation
0: After detection of a bus-off
alarm, keep the CAN chip in the
Bus-Off (Reset) status
status.
1: If possible, full reset of the
CAN chip and after detection of
a bus-off alarm, continue with
communication.
24
specific
get/set
BK_DO_FAU
LT_REACTIO
N_ON_RELE
ASE_PIO
USIN
T
Defines the behavior after
allocation of the polled I/O
connection
0: No activity (default)
1: Error behavior processing for
fieldbus coupler/controller
25
specific
get/set
BK_DO_FAU
LT_REACTIO
N_ON_RELE
ASE_COS
USIN
T
Defines the behavior after
allocation of the change of state
and cyclic
I/O connection
0: No activity (default)
1: Error behavior processing for
fieldbus coupler/controller
26
specific
get/set
BK_DO_FAU
LT_REACTIO
N_ON_RELE
ASE_ST
USIN
T
Defines the behavior after
allocation of the strobed
connection
0: No activity (default)
1: Error behavior processing for
fieldbus coupler/controller
40
specific
get/set
BK_static_anal
og_digital_inp
ut_mapping
UINT
Defines how the values for the
analog and digital input bits are
determined.
0000: All bits are digital.
0016: One word is analog, the
remaining bits are digital.
0032: Two words are analog, the
remaining bits are digital.
...
0xFFFF: All bits are handled as
“Module Type” (default).