WAGO-I/O-SYSTEM 750
Fieldbus Communication 157
750-806 Fieldbus Controller DeviceNet
TM
Manual
Version 2.0.0
Table 96: Instance 1
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Description
41
specific
get/set
BK_static_anal
og_digital_inp
ut_mapping
UINT
Defines how the values for the
analog and digital outputs bits
are
determined.
0000: All bits are digital.
0016: One word is analog, the
remaining bits are digital.
0032: Two words are analog, the
remaining bits are digital.
...
0xFFFF: All bits are handled as
“Module Type” (default).
(If the number of analog bits
exceeds the size of the process
image, all bits are mapped to
analog bits.)
42
specific
get/set
BK_specific_c
oupler_
behavior
UINT
Defines the fieldbus
coupler/controller functionality.
0xFFFF: All possible functions
are enabled. (Resetting a bit to 0
disables the related function.)
It is only possible to reduce the
functionality. Resetting to “1” is
ignored.
43
specific
get/set
BK_revision_s
etting
UINT
Defines the major and minor
revision attributes of the
fieldbus coupler/controller.
0xFFFF: The major and minor
revision attributes are set by the
firmware by default.
0xXX00: The minor revision is
set to 0.
0x03XX: The major revision is
set to 3.
All other values are also valid.
44
specific
get/set
BK_SAVE_
DYN_ASS_
INST
UINT
Saves instances created
dynamically in the non-volatile
memory (after turning on the
power supply, all stored
instances are created
automatically).
0: Saves no dynamic instances
1: Saves dynamic instances
45
specific
get
BK_LED_ERR_
CODE
UINT
Contains the error code
displayed using I/O LED blink
code.
46
specific
get
BK_LED_ERR_
ARG
UINT
Contains the error argument
displayed using I/O LED blink
code.
47
specific
get
BK_DIAG_VA
LUE
UINT
Contains diagnostic information
supplied from the I/O module.
This attribute must be read
before attribute 6 of this class.
This only contains valid data
when attribute 6 contains valid
data.