Table 11: Protections, G2.7
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.7.13
Stall protection
0
3
0
709
0 = No response
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
P2.7.14
Stall current
0.00
2 x I
H
A
I
H
710
P2.7.15
Stall time limit
1.00
120.00
s
15.00
711
P2.7.16
Stall frequency
limit
1.0
P2.1.2
Hz
25.00
712
P2.7.17
Underload protec-
tion
0
3
0
713
0 = No response
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
P2.7.18
UP From Torque
10.0
150.0
%
50.0
714
P2.7.19
UP Zero fre-
quency load
5.0
150.0
%
10.0
715
P2.7.20
Underload protec-
tion time limit
2.00
600.00
s
20.00
716
P2.7.21
Response to ther-
mistor fault
0
3
2
732
0 = No response
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
P2.7.22
Response to field-
bus fault
0
3
2
733
See P2.7.21
P2.7.23
Response to slot
fault
0
3
2
734
See P2.7.21
STANDARD APPLICATION
VACON · 39
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
2