Table 120: Selections for parameter ID310
Selection
number
Selection name
Description
0
Set minimum value to 0 mA/0 V
1
Set minimum value to 4 mA/2 V
311 ANALOGUE OUTPUT SCALE 234567 (2.3.6, 2.3.5.6, 2.3.3.6)
Scaling factor for analogue output. Use the given formula to calculate the values.
Table 121: Analogue output scaling
Signal
Max. value of the signal
Output frequency
Max frequency (parameter ID102)
Freq. Reference
Max frequency (parameter ID102)
Motor speed
Motor nom. speed 1xn
mMotor
Output current
Motor nom. current 1xI
nMotor
Motor torque
Motor nom. torque 1xT
nMotor
Motor power
Motor nom. power 1xP
nMotor
Motor voltage
100% x U
nmotor
DC-link voltage
1000 V
PI-ref. value
100% x ref. value max.
PI act. value 1
100% x actual value max.
PI act. value 2
100% x actual value max.
PI error value
100% x error value max.
PI output
100% x output max.
PARAMETER DESCRIPTIONS
VACON · 259
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
8