A
B
C
t = Par. ID508
t
par. ID515
RUN
STOP
fout
Fig. 69: DC-braking time when Stop mode = Ramp
A. Motor speed
B. Output frequency
C. DC-braking
509 PROHIBIT FREQUENCY AREA 1; LOW LIMIT 23457 (2.5.1)
510 PROHIBIT FREQUENCY AREA 1; HIGH LIMIT 23457 (2.5.2)
511 PROHIBIT FREQUENCY AREA 2; LOW LIMIT 3457 (2.5.3)
512 PROHIBIT FREQUENCY AREA 2; HIGH LIMIT 3457 (2.5.4)
513 PROHIBIT FREQUENCY AREA 3; LOW LIMIT 3457 (2.5.5)
514 PROHIBIT FREQUENCY AREA 3; HIGH LIMIT 3457 (2.5.6)
In some systems it may be necessary to avoid certain frequencies because of mechanical
resonance problems. With these parameters it is possible to set limits for the "skip
frequency" region.
VACON · 306
PARAMETER DESCRIPTIONS
8
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205