Table 78: Protections, G2.7
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.7.24
TBoard1 Numbers
0
5
0
739
0 = Not used
1 = Channel 1
2 = Channel 1 & 2
3 = Channel 1 & 2
& 3
4 = Channel 2 & 3
5 = Channel 3
P2.7.25
TBoard Flt. Resp
0
3
0
740
0 = No response
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
P2.7.26
TBoard1
Warn.Lim
-30.0
200.0
ºC
120.0
741
Set here the limit
at which the tem-
perature warning
will be activated.
P2.7.27
TBoard1 Flt.Lim
-30.0
200.0
ºC
130.0
742
Set here the limit
at which the tem-
perature fault
(F65) will be acti-
vated.
NXP drives only
P2.7.28
Brake fault action
1
3
1
1316
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
P2.7.29
Brake fault delay
0.00
320.00
s
0.20
1317
P2.7.30
System bus fault
3
3
3
1082
0 = No response
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
P2.7.31
System bus fault
delay
0.00
10.00
s
3.00
1352
P2.7.32
Cooling fault delay
0.00
7.00
s
2.00
751