Table 16: Input signals, G2.2
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.7
AI1 signal inver-
sion
0
1
0
323
Analogue input 1 ref-
erence inversion
yes/no.
P2.2.8
AI1 signal filter
time
0.00
10.00
s
0.10
324
Analogue input 1 ref-
erence filter time,
constant.
P2.2.9
****
AI2 signal selec-
tion
0.1
E.10
A.2
388
TTF programming
method used. See
P2.2.10
AI2 signal range
0
2
1
325
0 = 0-10V (0-20
mA**)
1 = 2-10V (4-20
mA**)
2 = Custom setting
range**
P2.2.11
AI2 custom set-
ting minimum
-160.00
160.00
%
0.00
326
Analogue input 2
scale minimum.
P2.2.12
AI2 custom set-
ting maximum
-160.00
160.00
%
100.00
327
Analogue input 2
scale maximum.
P2.2.13
AI2 signal inver-
sion
0
1
0
328
Analogue input 2 ref-
erence inversion
yes/no.
P2.2.14
AI2 signal filter
time
0.00
10.00
s
0.10
329
Analogue input 2 ref-
erence filter time,
constant.
LOCAL/REMOTE CONTROL APPLICATION
VACON · 51
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]