348 TORQUE LIMIT, SUPERVISION FUNCTION 34567 (2.3.14, 2.3.4.5, 2.3.2.5)
Table 133: Selections for parameter ID348
Selection
number
Selection name
Description
0
No supervision
1
Low limit supervision
2
High limit supervision
3
Brake-off control
(Application 6 only, see Chapter 8.3 External brake control
with additional limits (IDs 315, 316, 346 to 349, 352, 353).)
If the calculated torque value falls below or exceeds the set limit (ID349) this function
generates a message through a digital output depending on
1
.
the settings of parameters ID312 to ID314 (applications 3,4,5) or
2
.
to which output the torque limit supervision signal (parameter ID451) is connected
(applications 6 and 7).
349 TORQUE LIMIT, SUPERVISION VALUE 34567 (2.3.15, 2.3.4.6, 2.3.2.6)
Set here the torque value to be supervised by parameter ID348.
APPLICATIONS 3 AND 4:
Torque supervision value can be reduced below the setpoint with external free analogue
input signal selection and selected function, see parameters ID361 and ID362.
350 REFERENCE LIMIT, SUPERVISION FUNCTION 34567 (2.3.16, 2.3.4.7, 2.3.2.7)
Table 134: Selections for parameter ID350
Selection
number
Selection name
Description
0
No supervision
1
Low limit supervision
2
High limit supervision
If the reference value falls below or exceeds the set limit (ID351), this function generates a
warning through a digital output depending on
1
.
the settings of parameters ID312 to ID314 (applications 3,4,5) or
2
.
to which output the reference limit supervision signal (parameter ID449) is connected
(applications 6 and 7).