Table 36: Input signals, G2.2
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.39
AI3 signal range
0
1
1
143
0 = Signal range 0
—10 V
1 = Signal range 2
—10 V
P2.2.40
AI3 inversion
0
1
0
151
0 = Not inverted
1 = Inverted
P2.2.41
AI3 filter time
0.00
10.00
s
0.10
142
0 = No filtering
P2.2.42
***
AI4 signal selec-
tion
0.1
E.10
0.1
152
TTF programming
method used. See
P2.2.43
AI4 signal range
0
1
1
154
0 = Signal range 0
—10 V
1 = Signal range 2
—10 V
P2.2.44
AI4 inversion
0
1
0
162
0 = Not inverted
1 = Inverted
P2.2.45
AI4 filter time
0.00
10.00
s
0.10
153
0 = No filtering
P2.2.46
Actual value spe-
cial display mini-
mum
0
30000
0
1033
P2.2.47
Actual value spe-
cial display maxi-
mum
0
30000
100
1034
P2.2.48
Actual value spe-
cial display deci-
mals
0
4
1
1035
P2.2.49
Actual value spe-
cial display unit
0
29
4
1036
See ID1036 in
CP = control place
cc = contact
oc = opening contact
* = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
PID CONTROL APPLICATION
VACON · 109
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
5