This is the maximum time for a stall stage. An internal counter counts the stall time. If the
value of the counter goes above this limit, the protection causes the drive to trip (see ID709).
See Chapter 8.5 Parameters of stall protection (IDs 709 to 712).
Par. ID711
Trip area
t
Stall time counter
Stall
No stall
Trip/warning
ID709
Fig. 75: Stall time count
712 STALL FREQUENCY LIMIT 234567 (2.7.16)
The frequency can be set between 1-f
max
(ID102).
For a stall state to occur, the output frequency must be below this limit for a certain time.
See Chapter 8.5 Parameters of stall protection (IDs 709 to 712).
713 UNDERLOAD PROTECTION 234567 (2.7.17)
Table 172: Selections for parameter ID713
Selection
number
Selection name
Description
0
No response
1
Warning
2
Fault, stop mode after fault
according to ID506
3
Fault, stop mode after fault
always by coasting
See Chapter 8.6 Parameters of underload protection (IDs 713 to 716).
714 UNDERLOAD PROTECTION, FIELD WEAKENING AREA LOAD 234567 (2.7.18)
You can set the value of this parameter between 10.0—150.0 % x T
nMotor
. This value is the
limit for the minimum torque when the output frequency is above the field weakening point.
If you change parameter ID113 (Motor nominal current), this parameter goes automatically
back to its default value. See Chapter 8.6 Parameters of underload protection (IDs 713 to 716).
PARAMETER DESCRIPTIONS
VACON · 325
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
8